Electrical Engineering ⇒ Topic : IS Specifications
|
DJ
| |
IS Specifications : (1). Outdoor type distribution transformers (IS : 1180-1964) : Standard ratings : 16, 25, 40, 50, 63, 80 and 100 kVA No-load voltage ratios : 3300/433 V, 6600/433 V and 11000/433 V. Tappings : Shall be provided on h.v. side in 5 steps. The ranges shall be ± 2.5% and + 5% off-load tap changers to be used. Connections : LVY (Dy 11) with neutral brought out to a separate insulated terminal. Cooling : By low viscosity transformer oil. Conservator tank To be provided on transformer of rating 50 kVA or above. Limits of temperature rise : The following temperature rises shall be permitted over the ambient temperature of 45°C: Winding (temperature to be measured by resistance method) 55°C Oil (temperature rise to be measured by thermometer in the top oil) 45°C The above temperature rises are for ON, OB, OW type cooling. Impedance : 4.5°/,2 at 75°C, subject to the tolerance limit of 10%. | |
| |